Distributed Power Project Management
MORE
INNIO's Jenbacher Gas Engines Services Provider
MORE

Managers:

Head of the Service Department,

M. Manokhin

Chairman of the Board,
Honored Power Engineer of the Russian Federation

A. Svergin

equipment in operation:

all equipment

EQUIPMENT

We are ready to organize the energy supply of your enterprise using our gas engine power plants fleet. In our park there are power plants based on gas engines from leading world manufacturers.

Modular Power Plant ETS-J1870 1.5 MW

Модульная ГПЭС производства "ЭнергоТехСервис"

Parameters Units Value
Engine producer - Under request
Power (el.) kW 1501
Methane number (min) - 70
Efficiency (el.) % 42,1-43,4
Speed rpm 1500
Fuel Consumption
nm³/ h 375
Operating temperature °С –60...+45
Engine volume l 61,1
Size, L x W x H m 12,1 х 3 х 3
Weight kg 34 000
Voltage
kV 0,4 / 6,3 / 10,5
Oil replacement interval* r.hrs 4000
Overhaul Interval** r.hrs 60 000
Life Time r.hrs 240 000
Automation level      - III

Modular Power Plant ETS-W1375 / 1560 1.1 / 1.25 MW



Модульная ГПЭС производства "ЭнергоТехСервис"

Характеристика Ед. изм. Значение
Engine producer
- Under request
Power (el.)
kW 1100 / 1250
Methane number (min)
- 30
Efficiency (el.)
% 32/35
Speed
rpm 1000
Fuel Consumption
nm³/ h
from 300 / from 285
Operating temperature
°С –60...+45
Engine volume
l 115,4
Size, L x W x H
m 12,1 х 2,4 х 2,9 /
10,5 х 2,4 х 6,2
Weight
kg 31 000
Voltage
kV 0,4 / 6,3 / 10,5
Oil replacement interval* r.hrs
4000 / 6000
Overhaul Interval** r.hrs
до 65 000
Life Time
r.hrs
260 000
Automation level
     - III

* - the total thermal power with a tolerance of +/- 8% is indicated; cooling of exhaust gases to 120 0С, while working on biogas cooling of exhaust gases up to 180 0С. All indicators refer to the full load of the engine and can be changed in the  technical development process. Additional engine versions may be offered upon request. 


** - the gas flow rate is calculated for natural gas with a calorific value of 9.5 kW/NCM.


PARTNERS: